Pressure Systems 9022 Manuel d'utilisateur Page 104

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 194
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 103
Pressure Systems, Inc. NetScanner™ System (9016, 9021, & 9022) User’s Manual
www.PressureSystems.com
3 - 74
The Valve Position indexes (ii=12 and ii=0C) (for Model 9016 only) each have two states (00/01)
that when combined provide four (4) possible states of the C1/C2/C3/C4 internal valves. This
“Logical Rotary Switch” with four (4) positions is summarized in the following chart:
C1 Energized
C2 Not
(0C=01)
C2 Energized
C1 Not
(0C=00)
C3 Energized
C4 Not
(12=01)
PURGE
position
LEAK/CHECK
position
C4 Energized
C3 Not
(12=00)
CAL/RE-ZERO
position
RUN
position
Example:
! Send TCP/IP commands to 9016 module (via its connected socket) setting the
calibration valve to the CAL (or Re-Zero) position:
w1200" (Set RUN/CAL valve position)
w0C01 (Set CAL position)
Responses (both commands):
“A”
“A”
NOTE: If the programmer “knows” that the module is already in the RUN/CAL
valve mode, the first command above is optional. For more information, see
Figures 4.1 through 4.4 in Chapter 4.
Vue de la page 103
1 2 ... 99 100 101 102 103 104 105 106 107 108 109 ... 193 194

Commentaires sur ces manuels

Pas de commentaire